About the Product
Each EP-1S Series single-phase potential transformer features a resin-insulated coil and is fixed on supporting metal pieces on the front and back sides. Select models of the EP-1S Series can be used as an auxiliary power source for circuit breaker operation. All models, with their excellent moisture resistance and high insulation, are well-suited for humid locations. These indoor low-voltage potential transformers are furthermore characterized by great safety and a high-quality exterior.
Product Features
- Standard: IEC or IEEE
- Resin-insulated
- Indoor applications
- Well-suited to humid environments
- Burden: ≦ 500VA (Models: EP-1S1A ~ EP-1S6A)
- Models that can be used as an auxiliary power source for circuit breaker operation have a burden rating of up to 5000VA
Selection Table*
Model | Phase (ø) | Frequency (Hz) | Primary Voltage (V) | Secondary Voltage (V) | Burden / Accuracy | AC/BIL | Approx. Weight (kg) | Thermal Burden (kVA) |
EP-1S1A | 1 | 60 or 50 | 220〜600 | 110〜220 | 50(10)VA/3.0(1.0) | 3/- kV | 2 | – |
EP-1S2A | 100(35)VA/3.0(1.0) | 3 | – | |||||
EP-1S3A | 50(25)VA/1.0(0.5) | 4 | – | |||||
EP-1S4A | 200(100)VA/3.0(1.0) | 5 | – | |||||
EP-1S5A | 300(50)VA/1.0(0.5) | 8 | – | |||||
EP-1S6A | 500(200)VA/1.0(0.5) | 10 | – | |||||
EP-1S7A | **1000VA | 15 | 1kVA | |||||
EP-1S8A | **1500VA | 17 | 1.5kVA | |||||
EP-1S9A | **2000VA | 25 | 2kVA | |||||
EP-1S10A | **3000VA | 32 | 3kVA | |||||
EP-1S11A | **5000VA | 46 | 5kVA |
* Other standards and specifications available.
** If burden rating ≥ 1000VA, the PT can be used as an auxiliary power source for circuit breaker operation (accuracy N/A)